Uninterruptible power supply - UPS
Uninterruptible power supply - UPS was recalled on 7 May 2010 under EU Safety Gate alert 0731/10. Electric shock risk reported by Finland. The product poses a risk of electric shock because live parts are accessible when replacing the fuse and because the creepage distances are too small at several points.
| Alert Number | 0731/10 |
| Brand | König Computer |
| Category | Electrical appliances and equipment |
| Risk Type | Electric shock |
| Notifying Country | Finland |
| Country of Origin | Unknown |
| Model Number | Type: CMP-UPS650VA Bar Code: 5 412810 041589 |
| Published | 7 May 2010 |
Risk Description
The product poses a risk of electric shock because live parts are accessible when replacing the fuse and because the creepage distances are too small at several points.The product does not comply with the Low Voltage Directive (LVD) and the relevant European standard EN 60950.
Measures Taken
Type of economic operator to whom the measure(s) were ordered: OtherCategory of measure(s): Withdrawal from the market and recall from consumers ordered by the authorities.Date of entry into force: Unknown
Product Description
Uninterruptible power supply
⚡ What Should You Do?
This recall involves a electric shock hazard related to Uninterruptible power supply - UPS.
About this risk
This product has inadequate electrical insulation, faulty wiring, or other electrical defects that can cause electric shock during use.
Recommended action
Unplug the product immediately and do not use it. Do not attempt to repair it yourself. Contact the manufacturer or retailer for a recall remedy.
Who is at risk?
Anyone using the product, especially in wet environments such as bathrooms or kitchens.